Why the stop button is wired NC but shows NO in ladder

It looks backwards the first time you see it. It is not.

Step 1: the wiring

A stop button is wired normally closed (NC). When nobody touches it, current flows through it to the PLC input. Pressing it opens the circuit.

Why? If the wire breaks or a terminal comes loose, the circuit also opens, and the machine stops. A broken wire fails safe. If the stop were wired NO, a broken wire would mean the stop button silently does nothing.

Step 2: the input bit

Because current flows at rest, the PLC input bit (call it STOP_OK) is 1 when nobody presses stop, and 0 when someone does (or the wire breaks).

Step 3: the ladder contact

A ladder contact does not describe the physical button. It asks a question about the bit:

You want the motor rung to pass power while STOP_OK is 1, so you use an NO contact on STOP_OK. Physically NC button, logically NO contact.

  START    STOP_OK          MOTOR
--| |--+----| |------------( )--
 MOTOR |
--| |--+

The common mistake

Drawing an NC contact for the NC button gives a double inversion: the motor runs only while stop is pressed (or the wire is broken). If a ladder "works backwards", check this first.

Real emergency stops go further: they use safety-rated devices and a safety relay or safety PLC, not just a standard input.

Service Call: PLC Trainer walks through this in Basics lesson 2b.