How to read a 4–20 mA signal

The most common analog signal in a plant is a current loop. Once you know five numbers, you can read it.

The five numbers

CurrentMeans
4 mA0 % of range (live zero)
8 mA25 %
12 mA50 %
16 mA75 %
20 mA100 %

Formula: % = (mA − 4) ÷ 16 × 100. Example: a 0–100 psi transmitter reading 14.4 mA → (14.4 − 4) ÷ 16 = 65 % → 65 psi.

Why it starts at 4, not 0

The "live zero" lets you tell an empty tank from a dead wire. A healthy loop never sits at 0 mA.

Measuring without breaking the loop

Breaking a running loop to put your meter in series makes the PLC see 0 mA. That can trip alarms, shut down a process or start a pump. Better options:

Compare field, PLC and HMI

A loop check compares the same value at 0/25/50/75/100 % in three places: the transmitter, the PLC raw counts and the HMI display. If the loop current is steady but the PLC value jumps, the problem is inside the PLC (channel config or scaling), not the transmitter.