How to megger a motor safely

An insulation tester (megger) puts hundreds of volts on the windings. Done wrong, it can hurt you or destroy a drive. Done right, it takes ten minutes.

Safety first. Follow your site's lockout/tagout procedure and electrical safety rules. Only qualified persons should do this work. Never defeat, jumper or bypass any safety device or interlock to make a test easier — if a procedure seems to need that, stop and ask.

1. Lock out and tag out

Open the disconnect that feeds the motor circuit, apply your own lock and tag, and try the start to confirm it is isolated.

2. Verify zero energy

3. Disconnect the drive leads

Never megger through a drive. The test voltage can destroy the drive's output transistors. Disconnect the motor leads (U, V, W) from the drive or starter and keep them apart. Also disconnect any electronics on the motor circuit (encoders, thermistors, surge suppressors) per the manufacturer.

4. Test

5. Read the result

Hundreds of megohms: healthy. Falling towards a few megohms: moisture or ageing — investigate and trend it. Below about 1 MΩ: do not run it; dry out or repair. Your site or the motor maker may set different limits.

6. Discharge and restore

Let the tester discharge the winding (it holds a charge after the test). Reconnect the leads correctly, remove your lock only when everyone is clear, and prove the motor runs.

Practise the whole sequence, including the traps, in the Technician calls of Service Call: PLC Trainer.